We help you with questions in day-to-day use

Our quick help for your support:

FAQ (> LINK)

Operating instructions (> LINK)

Service hotline (> LINK)

Please have the serial number of the device ready whenever you contact us! Where to find it is described in the FAQ.

If the Air Curtain malfunctions, your responsible installer is the main contact person and will be happy to help you.

Air curtain information for users
Your contact

Do you need support? Get in touch with us. We will be happy to help you!

Contact us

FAQ

Here you will find answers to the most frequently asked questions about the operation and use of our Air Curtain systems.

» On the type plate in the revision cover
» If you have a TCX control unit (touch control unit), it is not necessary to open the device. In this case, you will also find the serial number in the system menu

Please carry out the following checks step by step.

  1. Check whether the fuse in the fuse box is switched on.
    » Switch on the fuse
  2. Check whether the main switch (optional extra) in the device is switched on.
    » Switch on the main switch
  3. Check whether the control panel is switched on (touch control panels only).
    » Press the on/off button on the control panel
  4. Check whether a fault is displayed on the control panel (touch control panels only).
    » Acknowledge the fault
    » Inform the installer about the fault
  5. Check whether the devices have the authorisation (BMS) to run.
    » Have the release issued
  6. Check whether the devices are in automatic mode and automatic contacts (e.g. door contact) are not connected
    » Temporarily change to manual mode and check whether the device is running
    » If not, inform the installer
  7. Check whether a timer is stored
    » Adjust the timer so that the device is activated

Please carry out the following checks step by step.

  1. Check whether the central heating in the building is switched on.
    » Switch on the heating and open the valves
  2. Check whether the Air Curtain is operating in winter mode.
    » Change the setting from summer to winter mode.
  3. Check whether the target air discharge temperature is too low (touch control panel only).
    » Increase the target air discharge temperature.
  4. Check whether the heat output is set too low (electric door air curtain only).
    » Increase the heat output. Caution: The heating level can correspond to the maximum fan level.
  5. Check whether the flow temperature at the air curtain is too low.
    » Contact the installer.

Often occurs at the beginning of the heating period, caused by soiling of the heating coil during the summer period when the heating coil was not used.

» Switch off the device and wait until the heating coil has cooled down
» Clean the heating coil and air intake grille with a vacuum cleaner or compressed air

  1. Check whether the filter is dirty or blocked.
    » Check, clean or replace the filter.
  2. Check whether the fan speed is set correctly.
    » Adjust the fan speed on the control panel.
  3. Check whether the air outlet system is set correctly
    » Change the setting of the air outlet system, this should aim at the doorstep
    » Rotate the Convergo air outlet nozzle by 180° if it is misaligned (see operating instructions for more information)
  4. Check whether fans are running properly
    » Contact installer

User-friendliness and reliability

Our Air Curtains are designed to be user-friendly. The controls are intuitive and designed to be operated by non-technical personnel. However, if you have any questions about our products, we will be happy to help you.

Contact us

Write to us!

Please fill out the contact form. Fields marked with * are mandatory.
We will get in touch with you as soon as possible.

Are you looking for instructions or technical data?
Your selection:
  • Air Discharge System: CONVERGO® pressure chamber nozzle system
  • Air Discharge Range:
  • Mounting position:
  • Area of application:
  • Shape:
  • Heating type:
  • Sound insulation:
  • Unit Length: Unit length made to measure
  • Fan technology: AC
Please enable JavaScript in your browser to complete this form.
Rückmeldung